Prototype  demo content — production content authored in Payload from taxonomy + Aprimo DAM The vision EN
Register / Sign in

Disconnectors and earthing switches 3DN0/4/6/7/8, 40.5 kV up to 550 kV, rated normal current up to 5000 A, short-time withstand up to 63 kA, motor or manual operation

3DN0/4/6/7/8
  • Part of a portfolio with 123,000 disconnectors delivered to over 110 countries, type-tested to IEC, ANSI and GOST standards
  • 3DN0 earthing switches: free-standing up to 550 kV, built-on versions for every disconnector type, switching of induced currents per IEC 62271-102 Class A, Class B or super Class B where required
  • 3DN4 vertical break: single pre-adjusted, routine-tested movable current path subassembly; locking system with double kinematics keeps the closed position short-circuit-proof
  • 3DN7 V-type up to 145 kV: very compact and economic, all three poles mountable on a single horizontal member; 3DN8 side-break serves the 40.5 kV level
  • Block/finger contact system without pressing springs — contact force is self-produced and increases under short-circuit conditions; arc restrictors (bus-transfer contacts) are available for all disconnector types, with an optional 1600 A bus-transfer current capability offered by most types
  • Poles ship pre-assembled and pre-adjusted; 3DV6/7 (aluminium housing, -60 to +55 °C) and 3DV8 (stainless-steel housing, IP 55) motor drives, also manually operable
Air-insulated substations, 40.5 kV up to 550 kVGuaranteed de-energisation and earthing of high-voltage equipment (3DN0)Substations with limited phase-to-phase spacing (3DN4 vertical break)Compact, wall- or ceiling-mounted arrangements up to 145 kV (3DN7 V-type)40.5 kV switchyards (3DN8 side-break)
Register / Sign in
Sign in to see your price, availability and framework terms for 3DN0/4/6/7/8.

Horizon-3 pattern: this exact page gains commerce powers on sign-in — the URL never changes.

SIMULATED · ASK-AN-EXPERT PILOT DEMO
Ask an expert about 3DN0/4/6/7/8

15 minutes with the right switchgear specialist — question in, booked call out. No email archaeology.

Checking availability…

3DN0/4/6/7/8 covers up to 40.5 kV of the disconnectors range (≤ 550 kV across the category, √ scale).

Specifications

Main

Type designations 3DN0 (earthing switches), 3DN4 (vertical break), 3DN6, 3DN7 (V-type), 3DN8 (side-break)
Product type High-voltage AIS disconnectors and earthing switches
Contact system Block/finger, spring-free self-produced contact force, graphite-silver (AgC) dry lubrication
Operating mechanism Motor (3DV6/7 or 3DV8) or manual; rated nominal torque 600 and 800 Nm, operational time < 15 s, IP 55
Bus-transfer capability (optional) Arc restrictors available for all disconnector types; optional 1600 A bus-transfer current capability on most types, type-tested with more than 100 operating cycles of current making and breaking
Maintenance interval 25 years
Standards Type-tested to IEC, ANSI, GOST; earthing switches per IEC 62271-102 Class A / B / super Class B where required

3DN0 — Earthing switches

Voltage levels Free-standing versions up to 550 kV; built-on versions for every disconnector type in the range
Rated normal current up to 1000 A
Rated peak withstand current up to 160/164 kA
Rated short-time withstand current up to 63 kA (1/3 s)
Lightning impulse withstand (1.2/50 µs), to earth and between phases 185 kV at 40.5 kV up to 1675 kV at 550 kV
Ambient temperature range -55 °C up to +55 °C
Icing class 10 / 20 mm

3DN4 — Vertical-break disconnector (HBF series)

Rated voltage 72.5 kV up to 550 kV
Rated normal current up to 5000 A
Rated peak withstand current up to 160 kA
Rated short-time withstand current up to 63 kA (1/3 s)
Lightning impulse withstand (1.2/50 µs), to earth / across isolating distance 325 / 375 kV at 72.5 kV up to 1550 / 1550 (+315) kV at 550 kV
Ambient temperature range -55 °C up to +55 °C

3DN7 — V-type disconnector (VR series)

Rated voltage 72.5 kV up to 145 kV
Rated normal current up to 3150 A
Rated peak withstand current up to 125 kA
Rated short-time withstand current up to 50 kA (1/3 s)
Lightning impulse withstand (1.2/50 µs), to earth / across isolating distance 325 / 375 kV at 72.5 kV up to 650 / 750 kV at 145 kV
Installation Free-standing, wall and ceiling installation possible

3DN8 — Side-break disconnector (SR0 series)

Rated voltage 40.5 kV
Rated normal current up to 2000 A
Rated peak withstand current up to 100 kA
Rated short-time withstand current up to 40 kA (1/3 s)
Lightning impulse withstand (1.2/50 µs), to earth / across isolating distance 185 / 215 kV

3DN6

Ratings No digitized ratings source in this library — detailed ratings available on request

Documents & downloads

Brochure Disconnectors and earthing switches — high-voltage portfolio brochure (SHVC, 2025) View online · Download PDF ⭳
Brochure Global Parts Services for high-voltage AIS disconnectors (2023) View online · Download PDF ⭳
Brochure Disconnectors and earthing switches — Siemens Energy Brazil brochure (current online edition) View online · Download PDF ⭳

Ordered designations

Representative orderable type designations of this family — searchable via the catalog search.

Register for pricing and availability on 3DN0/4/6/7/8.