Prototype  demo content — production content authored in Payload from taxonomy + Aprimo DAM The vision EN
Register / Sign in

Composite long-rod insulator 3FL6, load class ≤ 222 kN (SML 210 kN per PEG Ed. 7.1), 72.5 – 550 kV, one-piece HTV silicone housing on ECR FRP rod, suspension & tension

3FL6
  • Official product hierarchy load class ≤ 222 kN; the Power Engineering Guide Ed. 7.1 ratings tables state SML 210 kN with routine test load (RTL) 105 kN — the heaviest class in the PEG 3FL2–3FL6 lineup
  • One-piece HTV silicone rubber housing, one-shot injection molded over the rod and triple junction point — no traditional sealing system, no moisture ingress path
  • Boron-free ECR glass FRP core rod — brittle-fracture resistant, hydrolysis- and acid-resistant
  • Size-20 socket-and-ball plus heavy clevis 22L/22N, tongue 22L/22N, Y-clevis 22 and eye 25/30 couplings per IEC 60120 / IEC 60471 / IEC 61466-1; electrical withstand values match the lighter series at equal housing lengths
  • Routine tensile test at ≥ 50% of SML for ≥ 10 seconds on every insulator; corona rings standard above 170 kV (Ø210/Ø330/Ø420 mm by line voltage)
Overhead transmission line tension strings with high mechanical loadsOverhead transmission line suspension stringsHigh-pollution coastal and industrial areasLine surge arrester assemblies
Register / Sign in
Sign in to see your price, availability and framework terms for 3FL6.

Horizon-3 pattern: this exact page gains commerce powers on sign-in — the URL never changes.

SIMULATED · ASK-AN-EXPERT PILOT DEMO
Ask an expert about 3FL6

15 minutes with the right arresters & insulators specialist — question in, booked call out. No email archaeology.

Checking availability…

3FL6 covers 72.5–550 kV of the long-rod & station post range (≤ 800 kV across the category, √ scale).

Specifications

Main

Product family 3FL6
Product type Composite (silicone) long-rod insulator
Application Suspension and tension on overhead lines
Housing One-piece HTV silicone rubber, one-shot injection molding onto the rod
Hierarchy load class 3FL6 insulators ≤ 222 kN (official product hierarchy, Tension and Suspension Insulators 3FL)

Ratings

Specified mechanical load (SML) 210 kN per PEG Ed. 7.1 tables (hierarchy load class ≤ 222 kN; 3FL family spans 70 – 630 kN)
Routine test load (RTL) 105 kN
Highest voltage for equipment (Um) 72.5 – 550 kV (nominal system voltages 60 – 500 kV)
Section length 878 – 6,182 mm per the 3FL5/3FL6 technical data table (socket and ball; the family maximum-values table quotes 871 – 6,125 mm); length increments 52 mm, other lengths on request
Creepage variants Standard creepage (catalog code 3) or extra-high creepage (catalog code 4)
Sealing system System A (triple point directly overmoulded, family up to 210 kN) or System B (gap fully sealed with elastic silicone gel, family 100 – 630 kN)

Representative ratings (socket and ball, standard creepage; 3FL5/3FL6 shared table)

Um < 72.5 kV LIWL 449 kV · PFWL 160 kV · arcing 643 mm · creepage 1,702 / 2,288 mm (std / extra-high) · section length 878 mm (3FL6 061-3SB21-1XX1)
Um 123 kV LIWL 664 kV · PFWL 320 kV · arcing 1,059 mm · creepage 3,003 / 4,082 mm · section length 1,294 mm (3FL6 103-3SB21-1XX1)
Um 245 kV LIWL 1,220 kV · PFWL 571 kV · arcing 2,002 mm · creepage 6,092 / 8,344 mm · section length 2,282 mm · Ø210 mm corona ring HV side (3FL6 202-3SB21-1XS1)
Um 420 kV LIWL 1,971 kV · SIWL 1,229 kV · PFWL 732 kV · arcing 3,398 mm · creepage 10,645 / 14,625 mm · section length 3,738 mm · Ø210 / Ø330 mm rings (3FL6 347-3SB21-1SM1)
Um 550 kV LIWL 2,284 kV · SIWL 1,415 kV · PFWL 806 kV · arcing 4,361 mm · creepage 13,735 / 18,888 mm · section length 4,726 mm · Ø210 / Ø420 mm rings (3FL6 446-3SB21-1SL1)

Mechanical / environment

Core ECR glass (boron-free) FRP rod — brittle-fracture resistant, hydrolysis- and acid-resistant
End fittings Hot-dip galvanized forged steel or ductile cast iron, monitored circumferential crimping; couplings for 210 kN: Socket and Ball 20 (IEC 60120), Clevis 22L/22N and Tongue 22L/22N (IEC 60471 / IEC 61466-1), Y-clevis 22, Eye 25 or 30 (IEC 61466-1)
End-fitting connection lengths V Ball 20 = 135 mm · Socket 20 = 129 mm · Clevis 22L = 154 mm · Tongue 22L = 153 mm · Y-clevis 22 = 156 mm · Eye 25 = 153 mm
Field control Integrated grading ring in the junction; external corona rings standard above 170 kV: Ø210 mm line end at 245 kV, Ø330 mm at 300/362 kV, Ø210 ground + Ø330 line at 420 kV, Ø210 ground + Ø420 line at 550 kV
Pollution performance Strongly hydrophobic HTV silicone rubber — reliable even in coastal salt fog and dust-laden industrial air

Standards & certifications

Design & type testing IEC 61109, IEC 62217, IEC 60815, IEC 61466-1/-2; latest flyer additionally states ANSI C29.11, ANSI C29.12, CSA C411.4-16
Routine test Tensile load ≥ 50% of SML for ≥ 10 seconds on every insulator

Documents & downloads

Catalog excerpt 3FL silicone long rod insulators — Power Engineering Guide (Edition 7.1) section 4.10 with 3FL2 – 3FL6 ratings and the 3FL5/3FL6 technical data table View online · Download PDF ⭳
Flyer 3FL long rod insulators — Composite technology up to 800 kV View online · Download PDF ⭳
Brochure Our portfolio of surge arresters & composite insulators — overhead line solutions incl. 3FL composite insulators up to 800 kV (current online edition) View online · Download PDF ⭳

Register for pricing and availability on 3FL6.