| Product family | 3EX |
| Product type | Surge arrester monitoring devices and accessories |
| Portfolio | Surge counters, surge counters with leakage current meter, sensor & display, ACM Arrester Condition Monitor (basic/advanced), control spark gap, LCM 500 portable measuring system |
| Purpose | Early fault detection, recording of operating states and remaining service life as input to asset management; arrester service life up to 30 years without maintenance |
| Installation | Integrated into the arrester ground connection (counters, sensors, ACM, control spark gap); LCM 500 portable with clamp-on ammeter |
| Response sensitivity (8/20 µs) | 200 A |
| High-current impulse withstand (4/10 µs) | 100 kA |
| Resolution | 5 impulses per second |
| Leakage current indication (3EX5 050) | mA meter, peak value / √2, bilinear scale |
| Leakage current measuring range (3EX5 050) | up to 30 mA; up to 50 mA on special model 3EX5 050-2 |
| Remote indication | Optional passive auxiliary contact (3EX5 030-1, 3EX5 050-1) |
| Response sensitivity (4/10 µs and 8/20 µs) | 1000 A |
| Response sensitivity (30/60 µs) | 200 A |
| Response sensitivity (rectangular wave) | 100 A |
| Leakage current measuring range | mA meter, up to 20 mA, logarithmic scale |
| Sensor-to-display distance | up to 200 m; connecting leads from 3 m to 30 m per the HV product guide |
| Local measurement | Display provides a connection for local leakage current measurement (e.g. oscilloscope) via accessory measuring lead |
| Measured variables (basic) | Number of surge current impulses; total leakage current; 3rd harmonic of leakage current with temperature correction and harmonic compensation (3 LEDs) |
| Measured variables (advanced) | Surge current impulse analysis (time stamp, peak value, pulse width, energy content); total leakage current; 3rd-harmonic analysis; arrester energy absorption per impulse |
| Trend registration (advanced) | Daily leakage current measurement at user-defined time, stored for more than 5 years |
| Power supply | Solar — no external power, no batteries, no galvanic connection to the arrester main circuit |
| Data readout (advanced) | Wireless to PC via USB wireless module (3EX5 085 per the monitoring catalog; 3EX5 086 per the 2021 HV product guide) and free Service Tool software |
| System integration | Meets requirements of future ISCM systems (IEC 61850-ready) without hardware replacement; basic version upgradable to advanced without arrester modification |
| Enclosure | Fully encased in silicone with no hollow spaces — moisture penetration impossible |
| Surge counter | 3EX5 030; with auxiliary contact 3EX5 030-1 |
| Surge counter with leakage current meter | 3EX5 050; 3EX5 050-1; 3EX5 050-2 (50 mA) |
| Sensor / display | 3EX5 060 / 3EX5 062 |
| ACM basic / advanced | 3EX5 080-0 / 3EX5 080-1 |
| Control spark gap | 3EX6 040; 3EX6 020 |
| Portable live condition monitoring | LCM 500 — measures the 3rd-harmonic leakage current component without interrupting operation; Siemens-arrester correction data built into the software |
| Upgrade from ACM basic to ACM advanced | 3EX5 081 |
| ACM advanced (USB wireless module) | 3EX5 086 |
| Connecting lead (required for operation) | 3EX5 063- plus a length code (lengths from 3 m to 30 m) |
| Mounting bracket for surge counter | 3EX5 930 |
| Connection cable for monitors | 3EX5 952 |
| Earth lead | 3EX5 955 |
| Data access | 24/7 real-time data access to the actual arrester condition and historical data via app or web browser |
| Live alerts | Alert function for critical arrester conditions via email or push notification |
| Historical data | Historical data within a chosen time period |
| Event log | Shows the leakage current curve and the weather conditions at the time of a surge event |
| System integration | Integration into the Sens-family |