FIT Standard

FIT Standard

Fluid-immersed distribution transformer, standard incl. substation, ≤ 3.15 MVA

FIT Standard
  • Key element at the last step of the power grid — converts medium voltage (up to 36 kV) to low voltage at identical frequency for DSOs, municipalities and substations
  • Hermetically sealed tank with corrugated walls absorbing fluid volume change; open-system or oil-conservator designs alternatively available
  • Low no-load and load losses compliant with EU Ecodesign Directive 2009/125/EC and Regulation (EU) 2019/1783
  • Ester-filled sibling variant available: fire point above 300 °C, K-class per IEC 61039, readily biodegradable per OECD 301
  • Step-lap core of cold-rolled (optionally laser-treated) sheets and diamond-dotted-paper-bonded windings for low noise and high short-circuit capacity
Register / Sign in
Sign in to see your price, availability and framework terms for FIT Standard.

Horizon-3 pattern: this exact page gains commerce powers on sign-in — the URL never changes.

SIMULATED · ASK-AN-EXPERT PILOT DEMO
Ask an expert about FIT Standard

15 minutes with the right transformers specialist — question in, booked call out. No email archaeology.

Checking availability…

FIT Standard covers up to 36 kV of the distribution transformers range (≤ 52 kV across the category, √ scale).

Specifications

Main

Product type Fluid-immersed (oil-immersed) distribution transformer — standard variant incl. substation transformers
Family FITformer® / Siemens Energy fluid-immersed distribution transformer portfolio, GT hierarchy DT Fit Class 12
Function Conversion of medium voltage to low voltage at identical frequency — the link between the electrical grid and consumers
Applications Distribution grids (DSOs, municipalities), suburban, urban and industrial areas; compact substations
Insulating liquid Mineral oil; ester-filled variant available as separate class-12 sibling (FIT Stand. incl. Subst. ≤ 3.15 MVA Ester)
Delivery condition Fully assembled and fluid-filled; plug-and-play solutions available

Electrical ratings

Rated power ≤ 3,150 kVA (this class; family floor 50 kVA per Budapest factory ratings, family continues as FIT Large > 3.15 MVA)
Max system voltage Up to 36 kV
Secondary voltage Typically 250–800 V (usually 250 or 450 V per product page)
Rated frequency 50 or 60 Hz
Losses Low no-load and load losses per EU Ecodesign; low no-load noise via step-lap core assembly
Harmonics High withstand capability against harmonics

Construction

Tank Hermetically sealed with corrugated walls absorbing insulation-liquid volume change; alternatively open system or oil conservator; bolted (optionally welded) sheet-steel lid
Corrosion protection Sandblasted, multicoated surface; hot-dip galvanization on request
Core High-grade cold-rolled (optionally laser-treated) sheets, precision-cut, step-lap assembly — or precise winding technology at lower power ratings
Windings Copper or aluminum; LV from strip or flat wire, HV from round or profile wire; diamond-dotted epoxy-coated paper bonds windings for higher short-circuit capacity
Drying & filling Vacuum low-frequency heating (LFH) drying; filled with preheated insulation liquid while still in the plant
Digital option Sensformer® Basic connectivity/monitoring on request

Standards & testing

Product standards IEC, EN (per Budapest factory production details)
Ecodesign EU Ecodesign Directive 2009/125/EC and Regulation (EU) 2019/1783 of October 1st, 2019
Ester fluid classification K-class insulating liquid per IEC 61039; readily biodegradable per OECD 301; tank-rupture prevention improved up to 20% (ester variant)
Routine & special tests Voltage, temperature-rise, insulation-resistance, partial-discharge, harmonics and noise-level tests in factory HV test bay; short-circuit and vibration tests at internationally recognized institutes
Factory certifications ISO 9001, ISO 14001, ISO 45001, ISO 50001, ISO 3834-2 (Budapest DT factory)

Options & variants

Variant split per GT_Product_Hierarchy Rev03 (DT Fit, Class 12/13); power and voltage ceilings from Siemens Energy fluid-immersed DT factory-portfolio slides (Budapest: 50 kVA–5,000 kVA, up to 36 kV, 50/60 Hz) and ester properties from the insulation-fluids slide.

VariantRated powerMax system voltageNotes
FIT Standard incl. Subst. ≤ 3.15 MVA≤ 3,150 kVA36 kVMineral-oil filled; 50/60 Hz; IEC/EN; hermetically sealed tank
FIT Stand. incl. Subst. ≤ 3.15 MVA Ester≤ 3,150 kVA36 kVEster-filled: fire point > 300 °C, K-class per IEC 61039, readily biodegradable (OECD 301)
FIT Large > 3.15 MVA (related class)> 3,150 kVA (Budapest family up to 5,000 kVA)36 kVLarger fluid-immersed DTs; wider portfolio up to 30 MVA / 145 kV

Compatible accessories

Digital monitoring
Sensformer® Basic digital connectivity and monitoring
Monitoring & diagnostics
SITRAM® H2Guard Lite online hydrogen (DGA) monitor, 25–5000 ppm, Modbus/DNP3.0
Insulating fluid option
Biodegradable ester insulating liquid (synthetic or natural, K-class per IEC 61039)

Documents & downloads

Presentation Fluid-immersed distribution transformers — family overview & factory network PPTX · EN ·
Presentation Distribution Transformers — portfolio, variants & technical innovations PPTX · EN ·
Fact sheet SITRAM H2Guard Lite — online hydrogen monitoring for liquid-filled transformers View online · Download PDF (297 KB) ⭳

Register for pricing and availability on FIT Standard.