Prototype  demo content — production content authored in Payload from taxonomy + Aprimo DAM The vision EN
Register / Sign in

Composite post insulator 3FT6, HTV silicone housing, 120 mm ECR core, SCL 78 kNm, 0.5 – 5.5 m, AC/DC

3FT6
  • 120 mm (4.7") core-diameter class of the 3FT family (3FT2 – 3FT7, SCL 18 – 150 kNm), for station post and line post applications on both AC and DC systems
  • Only 3FT type listed with both shed-profile variants in the type overview: 3FT6-3 (creepage factor 3.5) and 3FT6-4 (creepage factor 4.2), per IEC 60815-3 (AC) / IEC 60815-4 (DC)
  • HTV silicone housing applied by multi-shot injection molding on an ECR fiberglass core; overmolded end fittings seal the triple point against moisture ingress
  • Lightning withstand > 3050 kV at maximum length; single-unit length 0.5 – 5.5 m in 12.5 mm increments, stackable; flange end fittings: tapped 8x M16 D127, through-holes 8x D24 D225
  • Designed and tested to IEC 61952 / IEC 62231 and ANSI C29.17 / C29.19; optional Factory Acceptance Tests (FAT) in Asia and Europe
Busbar support in HV substationsSupport insulator below HV equipmentInclined and braced line postJumper supportInterface and interline spacersComposite insulator crossarm (CICA)
Register / Sign in
Sign in to see your price, availability and framework terms for 3FT6.

Horizon-3 pattern: this exact page gains commerce powers on sign-in — the URL never changes.

SIMULATED · ASK-AN-EXPERT PILOT DEMO
Ask an expert about 3FT6

15 minutes with the right arresters & insulators specialist — question in, booked call out. No email archaeology.

Checking availability…

Specifications

Main

Product family 3FT6
Product type Composite post insulator (station post / line post)
Series 3FT composite post insulators, core classes 3FT2 – 3FT7
Current type AC and DC

Ratings

Core diameter 120 mm (4.7")
Specified Mechanical Load (SCL) 78 kNm (equivalent to ceramic breaking load)
Maximum Design Cantilever Load (MDCL) 39 kNm
Length 0.5 – 5.5 m single unit, in 12.5 mm increments; stackable
Lightning withstand > 3050 kV
Creepage factor (creepage/arcing) 3.5 (3FT6-3) or 4.2 (3FT6-4)
System voltage validation 3FT family validated by electrical-field simulations up to 800 kV system voltage; larger corona rings required at higher system voltages

Mechanical & environment

Housing HTV silicone rubber, multi-shot injection molded — aging-resistant, hydrophobic, UV-resistant
Core ECR fiberglass rod (electrical and corrosion resistant)
End fittings Tapped flange 8x M16 D127 · through-holes flange 8x D24 D225
Adhesion system Extensively tested primer system bonding silicone housing, fiberglass rod and end fittings, with continuous monitoring and strict quality control in production

Standards & certifications

Line post IEC 61952 · ANSI C29.17
Station post IEC 62231 · ANSI C29.19
Shed profile IEC 60815-3 (AC) · IEC 60815-4 (DC)
Testing Fully tested to IEC and ANSI standards; optional Factory Acceptance Test (FAT) in Asia and Europe

Documents & downloads

Flyer 3FT composite post insulators — Engineered for extreme performance View online · Download PDF ⭳
Datasheet 3FT6 type-specific datasheet — available on request PDF · EN ·

Ordered designations

Representative orderable type designations of this family — searchable via the catalog search.

Register for pricing and availability on 3FT6.

Register / Sign in

Request information

Our team will get back to you.