Live-tank circuit breaker 3AP5, 800 kV, FI arrangement, closing resistors (pre-insertion resistors) on a four-interrupter pole, up to 63 kA / 5,000 A, BIL 2,100 kV, FA stored-energy spring mechanism

3AP5-800
  • Closing-resistor variant of the 800 kV 3AP4 live-tank breaker: four interrupter units per pole plus pre-insertion resistors, delivered on request (manufacturer catalog, 2022, via the verified 3AP3 entry)
  • Documented US-market 800 kV class ratings shared across the 3AP 4/5 line: up to 63 kA rated breaking current, up to 5,000 A continuous, BIL 2,100 kV, power-frequency withstand 1,150 kV
  • Pre-insertion resistors limit TRV impacts in transmission line protection and smooth reclosing by dissipating trapped charge; configurable resistance values and externally adjustable pre-insertion times (US brochure, platform PIR option)
  • FA spring-spring (stored-energy spring) operating mechanism, scalable from 15 kV to 800+ kV and inherently maintenance-free, driving 3AP arc-assist self-blast interrupters
  • FI arrangement (one pole per separate base); live-tank units rated 245 kV and above ship in sub-assemblies to optimize installation time and cost
800 kV EHV transmission line protection where closing resistors limit switching transientsPower transformer switching and protectionRetrofit replacement of existing fault-interruption devicesSpace-constrained outdoor bays requiring 2- or 3-cycle interruption
Register / Sign in
Sign in to see your price, availability and framework terms for 3AP5-800.

Horizon-3 pattern: this exact page gains commerce powers on sign-in — the URL never changes.

SIMULATED · ASK-AN-EXPERT PILOT DEMO
Ask an expert about 3AP5-800

15 minutes with the right switchgear specialist — question in, booked call out. No email archaeology.

Checking availability…

3AP5-800 covers up to 800 kV of the circuit breakers range (≤ 800 kV across the category, √ scale).

Specifications

Main

Type designation 3AP5 = 3AP4 four-interrupter 800 kV live-tank breaker delivered with closing resistors on request (manufacturer catalog, 2022)
Design Live-tank circuit breaker, 4 interrupter units per pole, with closing resistors (pre-insertion resistors)
Closing resistors Pre-insertion resistors: limit TRV impacts in transmission line protection, smooth reclosing by dissipating trapped charge; various resistance values, externally adjustable pre-insertion times (US brochure)
Pole arrangement FI — one pole per separate base (hierarchy family 3AP5FI-800kV)
Operating mechanism FA spring-spring (stored-energy spring) mechanism; scalable design applied from 15 kV to 800+ kV, inherently maintenance-free
Arc-quenching medium SF6, 3AP arc-assist self-blast interrupter units
Installation Outdoor

Electrical — 800 kV class, 3AP 4/5 (US live-tank brochure, 2021)

Rated maximum voltage 800 kV
Rated continuous current up to 5,000 A
Rated breaking current up to 63 kA
Lightning impulse withstand voltage (BIL) 2,100 kV
Power-frequency withstand voltage 1,150 kV

Standards & lifecycle

Type testing Every circuit breaker tested to ANSI and IEC standards (US brochure)
Delivery Live-tank units rated 245 kV and above ship in sub-assemblies engineered to optimize installation time and cost (US brochure)

Electrical — IEC platform ratings, 3AP4/5 800 kV (2022 catalog, current online edition)

Rated voltage 800 kV
No. of interrupter units per pole 4
Rated short-duration power-frequency withstand voltage 830 kV
Rated lightning impulse withstand voltage 2,100 kV
Rated switching impulse withstand voltage 1,425 kV
Rated normal current up to 5,000 A
Rated short-time withstand current (1 s – 3 s) up to 63 kA
Rated break time 2 cycles
Rated operating sequence O-0.3 s-CO-3 min-CO or CO-15 s-CO
Rated frequency 50 or 60 Hz
Temperature range −60 up to +55 °C (catalog footnote: limited normal-current rating at more than +40 °C)
Maintenance after 25 years

Documents & downloads

Brochure High Voltage Dead Tank Circuit Breakers — US Catalog (includes live-tank 3AP 4/5 ratings up to 800 kV) View online · Download PDF ⭳
Catalog High-Voltage Circuit Breakers — from 72.5 kV up to 1100 kV (Siemens Energy, 2022) (current online edition) View online · Download PDF ⭳
Manual Operational manual, 3AP5 800 kV — available on request PDF · EN ·

Ordered designations

Representative orderable type designations of this family — searchable via the catalog search.

Register for pricing and availability on 3AP5-800.

Register / Sign in

Request information