Dead-tank circuit breaker 3AP1 DT, 72.5 kV, up to 40 kA, stored-energy spring drive

3AP1 DT-72.5
  • Single-break 3AP arc-assist interrupter clears up to 40 kA at 72.5 kV with 3-cycle interrupting time
  • Standard operation to -40 °C without tank heaters — unique to the 15-72.5 kV class of the dead tank portfolio
  • FA stored-energy spring-spring mechanism (FA 2 gang / FA 1 IPO) — the same maintenance-free drive used across the 15 kV to 550 kV dead tank portfolio
  • Class M2 mechanical endurance (10,000 operations) and Class C2 capacitive switching certification
  • Gang or independent pole operation (IPO) on a common frame; PSD point-on-wave switching, composite / extra-creep bushings and up to four CTs per bushing optional
Register / Sign in
Sign in to see your price, availability and framework terms for 3AP1 DT-72.5.

Horizon-3 pattern: this exact page gains commerce powers on sign-in — the URL never changes.

SIMULATED · ASK-AN-EXPERT PILOT DEMO
Ask an expert about 3AP1 DT-72.5

15 minutes with the right switchgear specialist — question in, booked call out. No email archaeology.

Checking availability…

3AP1 DT-72.5 covers up to 72.5 kV of the circuit breakers range (≤ 800 kV across the category, √ scale).

Specifications

Main

Type designation 3AP1 DT (GT hierarchy: 3AP1DT-72,5kV; US market: SPS2-72.5)
Design Dead tank — grounded metal-enclosed interrupter, single interrupter unit per pole
Interrupter 3AP arc-assist self-compression interrupter with rupture disk per interrupter
Operating mechanism FA stored-energy spring-spring drive, maintenance-free — FA 2 (gang) / FA 1 (IPO) at 72.5 kV per platform mechanism table
Pole operation Gang or independent pole operation (IPO) on common frame
Insulating / quenching medium SF6 (standard 72.5 kV breaker operates to -40 °C without tank heaters; the SF6/CF4 mixed-gas low-temperature option on the 3AP1 DT platform is documented for the 126-170 kV classes only)
Current transformers Up to four toroidal-core CTs per bushing (optional)
Bushings Porcelain or composite; extra-creep bushing option

Electrical

Rated maximum voltage 72.5 kV
Rated continuous current up to 3,500 A
Rated short-circuit breaking current up to 40 kA
Interrupting time 3 cycles
Lightning impulse withstand voltage (BIL) 350 kV
Chopped-wave withstand (2 µs) 452 kV
Closing and latching capability up to 108 kA

Mechanical / environment

Low-temperature capability Operation to -40 °C without tank heaters (standard feature of the 15-72.5 kV class)
Mechanical endurance Class M2 (10,000 operations)
Capacitive switching Class C2
Seismic behavior Low center of gravity of the dead tank base — higher seismic withstand capability (platform characteristic)
Delivery condition Manufactured and routine-tested in the USA (Jackson, MS facility); no in-field adjustments required on the operating mechanism

Standards & certifications

Circuit breaker standards Type tested to ANSI and IEC standards per manufacturer catalogs (specific standard numbers are not cited in the source documents)
Endurance classes Class M2 mechanical (10,000 operations), Class C2 capacitive switching — classes as defined in IEC 62271-100
Factory certifications ISO 9001:2015, ISO 14001:2015, OHSAS 18001:2007 (US manufacturing facility, Jackson MS)
Testing Every breaker routine-tested; platform type testing in PEHLA-network, IEC 17025-accredited laboratory (Berlin)

Electrical — IEC ratings, 3AP1 DT 72.5 kV (2022 catalog, current online edition)

Rated voltage 72.5 kV
No. of interrupter units per pole 1
Rated short-duration power-frequency withstand voltage 140 kV
Rated lightning impulse withstand voltage 325 kV
Rated normal current up to 3,150 A
Rated short-time withstand current (1 s – 3 s) up to 40 kA
Rated break time 2 cycles or 3 cycles
Rated operating sequence O-0.3 s-CO-3 min-CO or CO-15 s-CO
Rated frequency 50 or 60 Hz
Temperature range −60 up to +55 °C (catalog footnote: limited normal-current rating at more than +40 °C)
Maintenance after 25 years

Options & variants

All rows transcribed from ratings tables in the staged US dead tank portfolio catalog. The CPV2/CPV2S and Blue Circuit Breaker rows are sibling products offered at the same voltage class, shown for portfolio context — they are not 3AP1 DT configurations.

VariantRated voltageShort-circuit currentConfigurationCatalog evidence
SPS2-72.5 (US designation of the 72.5 kV dead tank)72.5 kVup to 40 kA3-cycle, gang or IPO on common frame, to -40 °C without tank heaters, up to 3,500 AUS dead tank portfolio catalog, SPS2 15 kV - 72.5 kV ratings table (p. 6)
SPS2-15.5 / SPS2-25.8 / SPS2-38 / SPS2-48.3 (lower-voltage frame siblings)15.5 / 25.8 / 38 / 48.3 kVup to 40 kA eachSame FA spring-spring drive and 3AP arc-assist interrupter, shared 15-72.5 kV platform page; BIL 110/150/200/250 kV respectivelyUS dead tank portfolio catalog, SPS2 15 kV - 72.5 kV ratings table (p. 6)
CPV2/CPV2S 72.5 kV live tank option72.5 kV40 kALive tank circuit breaker / circuit switcher, 4,000 A, BIL 350 kV, power-frequency withstand 160 kVUS dead tank portfolio catalog, live tank option table (p. 11)
Blue Circuit Breaker 72.5 kV DT (Clean Air vacuum, SF6-free sibling)72.5 kV40 kAVacuum interruption, 3,150 A, released 2021 (72.5 kV LT version released 2018); FA spring-spring drive, M2/C2US dead tank portfolio catalog, Blue Circuit Breaker release table (p. 12)

Documents & downloads

Catalog Siemens Energy High Voltage Dead Tank Circuit Breakers (US portfolio, SPS2 15-550 kV — includes SPS2 15 kV - 72.5 kV ratings) View online · Download PDF (1.8 MB) ⭳
Catalog High-Voltage Circuit Breakers — From 72.5 kV up to 1100 kV (2022) (current online edition) View online · Download PDF ⭳

Ordered designations

Representative orderable type designations of this family — searchable via the catalog search.

Register for pricing and availability on 3AP1 DT-72.5.